What We Do

Features



  • Online double conversion with DSP control
  • Input current harmonic:<5%
  • Optimization Battery group the quality of battery:16/18/20 pieces (optional)
  • High output power factor 0.99
  • wide input voltage range:120~276Vac
  • wide input frequency range:(50Hz:45~55Hz/60Hz:54~66Hz)
  • Support genrator input
  • Support economic()ECO
  • self testing while UPS startup
  • OPtions: SNMP card/Relay card/Paralel card
  • Cold start

Technical Specification

model MF1106L16 MF1106B16 MF1110L16 MF1110B16 MF3110L16 MF3120L16
Capacity (VA) 6000 10000 20000
Input
Nominal Voltage 220/230/240Vac 380/400/415Vac; (3Ph+N+PE)
Oprating Voltage Range 120~276Vac 304~478Vac
Oprating Frequencey Range 50Hz:45~55Hz;60Hz:54~66Hz(auto sensing)
Power Factor >0.99
Bypass Voltage range Max.Voltage:+15%(optional +5%,+10%,+25%)
Min.voltage:-45%(optional -20%,-30%)
Frequencey protection range:+10%
ECO range Same as the bypass
Harmonic distortion(THDi) <5%(100% linear load)
Generator input Support
Output
Rated voltage 220/230/240Vac
Power factor 0.9(standard)
Voltage regulation +-1%
Frequencey(line mode) +-1%/+-2%/+-4%/+-5%/+-10% of the rated frequency(optional)
Frequencey(Bat. mode) 50/60(+-0.2)Hz
Crest factor 3:1
Harmonic distortion(THDi) <2% with linear load,<5% with non linear load
Efficiency >92%, >93%
battery
DC voltage 192Vdc/216 & 240Vdc(optional)
Backup time Depends on the capacity of external batteries Estimated remaining time displayed on the LCD
Typical recharge time 6~8 hours (to 90% of full capacity)
Charge current Max.current 6A Max.current 10A
System Features
Transfer Time Utility to Battery:0ms;Utility to bypass:0ms
Overload line mode load<=110%:last 60min;<=125%:last 10min;<=150%:last 1min,>=150% shutdown UPS immediatly
short circuit Hold whole system
Overheat line mode:switch to bypass;Breakup mode:shutdown UPS immediatly
Low battery voltage Alarm and switch off
Self diagnostics Upon power on and software control
EPO Shutdown UPS immediatly
Battery Advanced battery management
Noise Supperession Complies with EN62040-2
Audible and visual alarm Line failure,Battery low,Overload,system fault
LED & LCD display Line mode,Backup mode,Eco mode,bypass mode,Battery low,Battery bad,Overload and UPS fault
LCD display Inpu voltage,Input frequency,Output voltage,Output frequency,load percentage,battery voltage,Inner Temprature and remaining battery backup time
Communication Interface USB,RS485,SNMP card,paralel card,Relay card(optional)
Environmental
Oprating temprature 0~40'c
Storage temprature -25~55'c
Humidity range 0%~95%(Non-condensing)
Altitude <1500m
Noise level <45d8
Physical
Dimension W*D*h(mm) 220*481*438 250*500*650 220*481*438 250*500*650 250*502*616
Net weight(kg) 18 kg 65 kg 20 kg 70 kg 35 kg  40 kg
STANDARDS
Safety IEC/EN62040-1;IEC/EN60950-1
EMC IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4;IEC61000-4-5;IEC61000-4-6;IEC61000-4-8;